MPC and MGCP

Monitoring of Power Consumption and of the Grid Connection Point: reading measurements, resolving what they mean, and the PV curtailment factor.

Monitoring of Power Consumption reports what an appliance is drawing. Monitoring of the Grid Connection Point reports the same quantities at the building's boundary with the grid. They are the same measurements named from two sides, and they share their implementation here.

This machinery is not only MPC and MGCP. The same "describe a measurement twice and read it back" serves eleven use cases: those two, EVCEM and EVSOC for a car, MOI, MPS, MOB and COB for an inverter, a PV string and a battery, and MDT, MRT and MOT for the hot water, a room and the outdoors. Each adds vocabulary — charged energy, state of charge, DC power, yields, insulation resistance, three different temperatures — and none adds mechanism.

A measurement without its description means nothing

A notification looks like this:

{"measurementId": 3, "value": {"number": 2300}}

Which is 2300 of what, on which phase, scaled by how much? None of that is in the message. It is in two other functions — the measurement descriptions and the electrical connection descriptions — which a Monitoring Appliance reads once at commissioning and keeps.

So the appliance reads them, subscribes, and resolves everything afterwards:

use eebus::model::ElectricalConnectionPhaseName as Phase;

readings.total_power();                                        // Some(2300.0) watts
readings.value(&Measurand::on(Quantity::Current, Phase::A));   // Some(3.5) amperes

Two rules the crate enforces rather than leaving to the caller:

  • A value whose description never arrived is dropped, not guessed at.
  • A value flagged error or outOfRange is not handed back as a number. §2.5.2 lists the three states together and says the same of both abnormal ones: they "SHALL be ignored by the Monitoring Appliance" ([MPC-003]) — so a meter reporting 14 kW outOfRange against an 11 kW constraint is not "high but real". Reading::usable() returns None for both; the raw value field is still there for a display.

When the reading was taken, not when it arrived

[MPC-002], [MDT-002], [MRT-002] and [MOT-002] all permit a timestamp on the value and forbid the history that would otherwise justify one. Reading::timestamp carries it verbatim, and Readings::read_at hands it back beside the value:

let (degrees, taken_at) = readings.read_at(&mrt::MEASURAND)?;

Arrival time is no substitute. An appliance subscribes rather than polls, so a notification arrives when something changes, and a room holding its temperature sends nothing at all. Ageing readings by arrival discards the ones most likely to still be true, and cannot tell that room from a sensor that died an hour ago.

Most peers send none, so taken_at is usually None; what that means is the application's call. A Monitored Unit on this side stamps with MonitoredUnit::set_at, or hvac::mrt::temperature_at and its two siblings. set sends no timestamp: the engine's clock is monotonic uptime, not a time of day.

One element, two things

timestamp is AbsoluteOrRelativeTimeType: an instant or a span, and nothing in the element says which. taken_at()?.parse() reads whichever arrived:

use eebus::model::TimeValue;

let taken_at = match reading.taken_at()?.parse()? {
    // An instant on the peer's own calendar.
    TimeValue::Absolute(stamp) => stamp.unix_seconds(),
    // An age: the unit measured this long before it sent the message.
    TimeValue::Relative(_) => reading.taken_at_relative_to(arrived).map(|d| d.as_secs() as i64),
};

A relative timestamp is an age, so Reading::taken_at_relative_to subtracts it from the arrival time, saturating at zero. An absolute one is xs:dateTime, not RFC 3339, and unix_seconds() is None when it carries no offset; as_timestamp() says whether it could be read at all. How far to trust a peer's clock stays the application's policy. See Times.

What silence means

A value that has not arrived for ten minutes is either a peer that stopped answering or one with nothing to say. The descriptors say which; see Who has to subscribe, and what silence means.

Curtailment

MGCP scenario 1 carries the photovoltaic curtailment factor: how much of what the plant could produce it is currently allowed to. It is the measurement that closes the loop with LPP — a limit was sent, and this is what actually happened.

[MGCP-011] states it as an equation rather than a value:

P_PV,feed-in  ≤  PLF_PV,feed-in,max,pct  ×  Σ P_PV,AC,nom

The factor is what crosses the wire. The sum of the installed systems' nominal peak power is a property of the building that no EEBUS message carries, so only the two together are a number of watts — and it is the watts an energy manager acts on. In Germany that number is the export ceiling of EEG §9.

FeedInLimit keeps both terms, which is what stops a caller acting on a percentage as though it were a power:

use eebus::usecases::mgcp::FeedInLimit;

// 70 % of a 12 kWp array: the classic §9 configuration.
let limit = FeedInLimit::new(70.0, 12_000.0);
assert_eq!(limit.watts(), 8_400.0);
assert!(!limit.permits(9_000.0));

// And the value LPP is written with, which is how an inverter hears about it.
let write = limit.as_production_limit();

The factor's keyId is the connection point's, not yours

MGCP Table 23 spells the identifier <k1#(1..1)>: the device picks the number and fixes the name, pvCurtailmentLimitFactor. A DeviceConfiguration feature carries every configuration key the device has, so key 1 on a real connection point is as likely to be its installed peak power in watts — a number that reads as a perfectly plausible percentage and becomes a wrong export ceiling with nothing on the wire to say so.

Curtailment is the reader: hand it both functions, in whatever order they arrive, and it holds the description beside the value.

use eebus::usecases::mgcp::{self, Curtailment};

let mut factor = Curtailment::new();
factor.describe(&mgcp::curtailment_description());
assert_eq!(factor.apply(&mgcp::curtailment_value(70.0)), Some(70.0));
assert_eq!(factor.limit(12_000.0).map(|l| l.watts()), Some(8_400.0));

factor_percent is None until both halves are in, and None is not zero — an unread message is not a curtailment, and treating it as one stops a roof exporting.

Or let the actor do it

MonitoringApplianceActor serves the whole use case. monitoring::locate finds the connection point's DeviceConfiguration feature next to its measurements, attach reads the description and subscribes, and the factor arrives as an event:

match appliance.handle_event(&event) {
    Some(MonitoringEvent::CurtailmentChanged { unit, factor_percent }) => {
        let ceiling = appliance.feed_in_limit(&unit, 12_000.0);
    }
    _ => {}
}

unit is a UnitId — a device and an entity — because one device is regularly several units: a heat-pump gateway announces one HVACRoom per room, each with its own Measurement feature. attach takes one peer per entity, MonitoredUnitPeer::id() produces the key, and readings, curtailment, feed_in_limit and detach all take one.

There is no mgcp::curtailment_client_feature to go with curtailment_feature, and the asymmetry is the specification's: LPC IG §3.3 asks each actor to hold one client feature with featureType Generic for all of its client functionality. A Monitoring Appliance reads a Measurement server for scenarios 2 to 7 and a DeviceConfiguration server for scenario 1 from the same one — limitation::client_feature, the same constructor an Energy Guard uses.

Every feature a peer might not have

MGCP §3.2.2.2.1 ties each feature type to the scenarios that use it, and then says the presence indications are "meant relative to the ones of the according Scenario stated in Table 1". DeviceConfiguration belongs to scenario 1; Measurement and ElectricalConnection belong to scenarios 2 to 7. So which features a peer serves depends on which scenarios it implements, and MonitoredUnitPeer carries all three as Option:

let peer = monitoring::locate(remote, mgcp::NAME, actors::GRID_CONNECTION_POINT)?;
peer.measurement;            // Option: absent on a scenario-1-only connection point
peer.electrical_connection;  // Option: absent wherever there are no phases to describe
peer.curtailment;            // Option: MGCP scenario 1, and absent from MPC entirely

attach reads only what is there. What locate does require is that the peer serve at least one of them: a peer announcing the use case and none of its features would otherwise sit in the actor's list for the life of the connection, waiting for notifications that cannot come.

That is also what lets a hot water tank in through the same door. A DHW circuit has no ElectricalConnection at all — MDT Table 6 gives the use case one feature — so it has a locate of its own, and what it returns goes into the same actor:

use eebus::usecases::hvac::mdt;

let tank = mdt::locate(remote)?;          // measurement only; no phases to describe
appliance.attach(&mut engine, tank, now); // the same actor as a grid connection point

So do the two temperatures a building is planned against — hvac::mrt for a room and hvac::mot for outdoors — which are the same shape again. A room comes in the plural:

use eebus::usecases::hvac::mrt;

for room in mrt::locate_all(remote) {     // one HVACRoom entity per room
    appliance.attach(&mut engine, room, now);
}