MOI, MPS, MOB and COB: what an inverter, a string and a battery report, and the only control use case outside the grid pair.
Four use cases about the machines on the generation side of a building, and they nest the way the hardware does: an inverter with PV strings on one DC bus and a battery on another, presenting one AC connection to the house.
| Use case | Actor | What it answers |
|---|---|---|
| MOI — Monitoring of Inverter | Inverter | apparent and reactive power, yields, cos φ |
| MPS — Monitoring of PV String | PVString | what each string is producing, on its DC side |
| MOB — Monitoring of Battery | Battery | power, current, voltage, energy, state of charge |
| COB — Control of Battery | Inverter | what the battery should do |
Layering, not repetition
MOI is explicit about it (§2.5.1): an inverter SHALL also support MPC, which carries the ordinary AC values — active power, current, voltage, frequency. MOI adds only what is specific to a machine converting DC into AC: apparent and reactive power, the power factor, the four yield counters, the nameplate, and a component temperature.
The same nesting appears in the entity tree. A PVString and a Battery are sub-entities of an Inverter, and an installation with two roofs has two PVString entities under one inverter — which is the point of MPS rather than MGCP. A shaded or failing string is invisible in a building's total and obvious in its own measurement.
One measurement layer, eleven use cases
MOI, MPS and MOB are built on the same usecases::monitoring machinery as MPC, MGCP, EVCEM, EVSOC, COB and the three HVAC thermometers. What they add is vocabulary, not mechanism:
use eebus::usecases::mob;
use eebus::usecases::monitoring::{Measurand, Quantity};
let mut battery = mob::monitored_unit(1)
.with(Measurand::unphased(Quantity::DcPower))
.with(Measurand::unphased(Quantity::StateOfCharge));Measurand::unphased is the DC counterpart of total and on. A direct-current measurement has no phases, and the parameter description omits acMeasuredPhases rather than defaulting it to abc — a client waiting for phase information on a DC measurement would wait forever.
Three of a battery's values are easy to confuse and are separate quantities here for that reason:
stateOfChargeis a percentage — how full.stateOfEnergyis watt-hours — how much is in there.useableCapacityis watt-hours — how much it could hold, after ageing.
A client that read stateOfEnergy as a percentage would see a 12 kWh battery as 12 000 per cent full.
COB — the other control use case
Everything above reads. COB writes, and it is the only control use case in the crate outside the LPC/LPP pair — with, unsurprisingly, the same safety shape: a heartbeat, a failsafe state, a Failsafe Duration Minimum between two and twenty-four hours, and a state machine that fails towards a known-safe number rather than towards the last thing it was told.
Its own idea is that a manager may control a battery in either of two frames:
use eebus::usecases::cob::{ControlMode, SetpointWrite};
// "Charge at 3 kW."
inverter.on_control_mode(ControlMode::Power, true, now);
inverter.on_setpoint(&SetpointWrite::active(3_000.0), true, now);
// Or: "hold the grid connection at zero, and work the rest out yourself."
inverter.on_control_mode(ControlMode::Pcc, true, now);
inverter.on_setpoint(&SetpointWrite::active(0.0), true, now);pcc is the mode that self-consumption optimisation actually wants, and the reason the inverter rather than the manager does the arithmetic: an inverter reacts to the grid connection in milliseconds, and a manager on a network cannot.
Two details bite:
The sign convention is passive ([COB-001/1]): positive is consumption, negative is production. A setpoint of −3 000 W is discharging at three kilowatts, and a caller that gets the sign wrong charges when it meant to discharge.
Which setpoint power mode uses depends on the machine. A battery inverter has only an AC side, so [COB-011] sets AC power. A hybrid inverter also has PV strings on its DC bus, so [COB-012] sets DC power and the AC side is whatever the sun leaves over. Telling a hybrid inverter an AC number would not say what the battery should do, which is why InverterKind is a constructor argument rather than something to remember.
Deactivated is not zero
[COB-917] is the rule most easily got wrong. A deactivated setpoint hands the inverter to its default setpoint, which is a configured number — not nought, and not the last thing the manager said. EffectiveControl names which of the four is driving the machine:
EffectiveControl::Setpoint(3_000.0) // the manager's number
EffectiveControl::Default(-500.0) // deactivated or expired [COB-917]
EffectiveControl::Failsafe(0.0) // the manager went quiet [COB-913]
EffectiveControl::Autonomous // the inverter's own logicIn a household that is being billed for what the battery does, which of those four applied is the whole question — and it is not visible on the wire.