opcua-kit

Capture device metadata

On this page

A capture records the metadata a device exposes for the signals in your contract. It reads their declarations and requested engineering units. To record a process value, use the client or meter commands.

Prepare the field laptop

Install the CLI with cargo install opcua-kit --locked --features cli. Supply a reviewed contract, the server leaf certificate obtained through the site’s trust process, and your client application certificate and matching unencrypted RSA private key. The CLI reads PEM and DER files. Restrict access to the private key.

Use the server application URI from the contract and an endpoint whose DNS name or IP address appears in the server certificate. The CLI takes its client application URI from the single URI in the client certificate’s subject alternative names. Set --client-uri when you also want to check that identity against an expected value. The server must trust the client certificate. OPC UA application certificates

The default session uses Basic256Sha256 with SignAndEncrypt and the anonymous principal. For a named account, set the contract principal to username:<account> and pass --username <account> --password-file reader.secret. Select a different supported channel policy with --security-policy. Endpoint and account selection

Check the setup offline

Run preflight with the exact contract, endpoint and credentials for the visit. Specify the port explicitly.

opcua-kit capture --preflight --contract plant.json --endpoint opc.tcp://ahu-01.example:4840 \
  --server-cert server.der --client-cert client.pem --client-key client-key.pem

Preflight checks the contract, the selected principal, certificate validity and usage, endpoint host, application URIs and private-key match. It runs locally with the network disconnected. Exit 0 means the local configuration passed. A live capture verifies the responding peer and exercises its read permissions.

Capture and assess

opcua-kit capture --contract plant.json --endpoint opc.tcp://ahu-01.example:4840 \
  --server-cert server.der --client-cert client.pem --client-key client-key.pem \
  --output before.json
opcua-kit check --contract plant.json --snapshot before.json

Capture writes one row per signal in contract order. It resolves each namespace URI in the session, reads the requested declarations, and verifies each selected EngineeringUnits property before reading its value. An unresolved namespace leaves an identity-only row. A valid snapshot can contain incomplete evidence. check exits 0 for a match, 2 for a mismatch or 3 when only incomplete evidence prevents a decision.

The collection budget includes session setup and shutdown. It defaults to 30 seconds. Use --timeout to select 1–300 seconds. Each service request has a timeout of at most 60 seconds. A successful capture atomically replaces the output file. If acquisition fails, an existing snapshot stays intact. Omit --output to write JSON to stdout.

To compare a later visit, save the new capture under a different name. For an immediate decision in automation, pipe the snapshot to opcua-kit check --contract plant.json --snapshot - --json. Automation and evidence

ObservationWhat to check
Server certificate rejectedVerify the endpoint name, server application URI and approved leaf. Obtain a rotated pin through the site’s trust process.
BadNodeIdUnknownCheck the namespace URI and identifier for the selected device.
BadUserAccessDeniedVerify read permissions for the selected account.
Missing or unidentified EngineeringUnitsInspect the property’s declared type, namespace and unit ID in the device model.
Ambiguous or conflicting unit targetCheck for one local scalar EUInformation property. A contracted process signal cannot also supply a unit property’s value.